SELF REGULATING TAPES
ESR®-M
![]()
Eltrace Self Regulating heating tape - medium size
THE SOLUTION TO FROST PROTECTION OF YOUR WATER LINES AND LOW TEMPERATURE PRODUCT LINES
Applications:
The ELTRACE ESR-M is a self regulating heating tape designed for frost protection, for pipes, gutters, sprinkler installations and storage tanks, indoors and outdoors, and also temperature maintenance of pipes. The black TPE outer jacket ensures the required UV resistance.
Advantages:
ELTRACE Self regulating tapes can be cut to length on site and stored in rolls. The power output of the conductive heating element increases or decreases in response to ambient temperature changes. This self-regulating effect occurs at every point along the length of the cable thereby adjusting the power output to the varying ambient temperature condition. ELTRACE ESR-M is available in stock.
The Thermoplastic elastomer (TPE) insulation provides excellent electrical resistance and protects the heating tape against moisture.
As an overjacket the Fluoropolymer offers increased chemical and abrasion resistance and good compatibility with potable water. Fluoropolymers are also UV-resistant
Technical properties:
Voltage Rating:
AC 230 V 50 Hz
120V on request
Min use temperature: -30°C
Max. surface temperature:
De-energized : 65°C
Energized : 85°C
Power grade:
10 W/m at 10°C
15 W/m at 10°C
20 W/m at 10°C
25 W/m at 10°C
Available Version :
ESR-M-BO: Thermoplastic elastomer (TPE) overjacket (10, 15, 20, 25 W/m)
ESR-M-BOT: Fluoropolymer overjacket (10, 15, 20, 25 W/m)
Heating element: Cross linked polyolefin
| Reference : ESR-M- |
-M-10-BO -M-10-BOT |
-M-15-BO -M-15-BOT |
-M-20-BO -M-20-BOT |
-M-25-BO -M-25-BOT |
| Bus bar Tinned Copper | 1.00 mm² | 1.00 mm² | 1.00 mm² | 1.00 mm² |
| Size with TPE Size with Fluoropolymer |
10.5 × 6.0 10.3 x 5.8 |
10.5 × 6.0 10.3 x 5.8 |
10.5 × 6.0 10.3 x 5.8 |
10.5 × 6.0 10.3 x 5.8 |
| Minimum bending radius | 25 mm | 25 mm | 25 mm | 25 mm |
| Min installation Temp. | -30°C | -30°C | -30°C | -30°C |
| Circuit breaker size (C type) |
16 A | 16 A | 16 A | 16 A |
| Start-up Temp. +10°C -15°C -20°C |
154m 136m 118m |
139m 89m 78m |
110m 71m 58m |
83m 56m 47m |
| < Précédent | Suivant > |
|---|